PLX31-EIP-MBS4 PROSOFT Central control module

ProSoft Technology’s EtherNet/IP™ to Modbus® Serial communication gateway
allows high-speed bi-directional data transfers between EtherNet/IP™ PACs or
devices and Modbus®-enabled PACs or devices.
EtherNet/IP™ PACs include Rockwell Automation® ControlLogix® and
CompactLogix™, as well as several Schneider Electric® controllers. Modbus® Serial
devices are widely used in nearly every industry and include SCADA systems and
Power Monitors. Four ports allow for connectivity of up to 400 Modbus® Serial
devices, reducing the amount of gateways required for your application.
In addition, the gateway includes several features that allow for simplified integration,
reduced commissioning time and optimized performance.
Category:
  • Email:cindy@justwellcenter.com
  • Phone:+86 13376981664
  • Whatsapp:+86 13376981664
  • Amy

Description

Brand: PROSOFT          Model number:PLX31-EIP-MBS4

Colour:new                  Warranty: 12 months

Lead Time:3-day working day   Country of origin: Japan

Price: Please contact us         Product weight: 2.5kg

Product Dimensions:

ProSoft Technology’s EtherNet/IP™ to Modbus® Serial communication gateway
allows high-speed bi-directional data transfers between EtherNet/IP™ PACs or
devices and Modbus®-enabled PACs or devices.
EtherNet/IP™ PACs include Rockwell Automation® ControlLogix® and
CompactLogix™, as well as several Schneider Electric® controllers. Modbus® Serial
devices are widely used in nearly every industry and include SCADA systems and
Power Monitors. Four ports allow for connectivity of up to 400 Modbus® Serial
devices, reducing the amount of gateways required for your application.
In addition, the gateway includes several features that allow for simplified integration,
reduced commissioning time and optimized performance.

Features
 Data prioritization: Multiple I/O connections allow you to set RPIs for status and/or control data, optimizing Ethernet bandwidth.
 Includes an embedded EDS Add-On Profile, allowing for simplified integration and reduced commissioning time.
 Includes a SD card slot (SD card optional) for storing configuration files. This can be used for disaster recovery.
 Four serial ports allow for connectivity of up to 400 Modbus® devices, reducing the amount of gateways required for your
application.
 ProSoft Discovery Service: This utility allows your PC to see the gateway and change its default IP address without being on the
same subnet.
 Secure module configuration via module switch (v1.04 and greater).
 Up to 10,000 16-bit registers can be used to exchange large amounts of data.
Specifications
EtherNet/IP™ Specifications
Specification Description
Number of Class 3
Server Connections
5
Supported PLC Types PLC2, PLC5, SLC, CLX, CMPLX, MICROLX
Supported Message
Types
PCCC and CIP
Class 3 Client
Connections
Connected: 2
Unconnected: 1
Number of Class 1 I/O
Connections
8
I/O connection sizes 248/248
Max RPI time 5 ms per connection
CIP Services Supported 0x4C – CIP Data Table Read
0x4D – CIP Data Table Write
CIP Generic
Command List Support for 100 commands per Client, each configurable for
command type, IP address, register to/from addressing and
word/bit count.
Command Sets PLC-2/PLC-3/PLC5 Basic Command Set
PLC5 Binary Command Set
PLC5 ASCII Command Set
SLC500 Command Set
Modbus Serial Specifications
Specification Description
Command List Up to 100 commands per Master port, each fully configurable
for Function Code, slave address, register to/from addressing
and word/bit count.
Supported Modbus
Function Codes
1: Read Coil Status
2: Read Input Status
3: Read Holding Registers
4: Read Input Registers
5: Force (Write) Single Coil
6: Preset (Write) Single
Holding Register
15: Force (Write) Multiple Coils
16: Preset (Write) Multiple
Holding Registers
22: Mask Write Holding Register
(Slave Only)
23: Read/Write Holding
Registers (Slave Only)
Software configurable
communication
parameters
Baud rate: 110 baud to 115.2 kbps
Parity: None, Even, Odd
Data Size: 7 or 8 bits
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds
Modbus RTU mode (binary) with CRC-16
Modbus ASCII mode with LRC error checking
Floating Point Data Floating point data movement supported,
including configurable support for Enron and Daniel
implementations
Polling of Command List Configurable polling of command list, including continuous
and on change of data, and dynamically user or automatic
enabled.
Status Data Error codes available on an individual command basis. In
addition, a slave status list is maintained per active Modbus
Master port.
Node Address 1 to 247 (software selectable)
RS Interface RS232, RS422, and RS485
Transmit and Receive
Buffer Size
255 byte Transmit character length with 0 to 65535
millisecond delay between each transmitted character

 

Shipping Port: Xiamen, China

Payment: Bank of Chicago, Bank of Singapore

Express cooperation: fedex, DHL, UPS and your express account

Service: Professional Sales provides 24 hours /7 days online service

Please make an inquiry for more models:

PROSOFT MVI56-GSC
PROSOFT MVI56-LTQ
PROSOFT MVI56-PDPMV1
PROSOFT MVI69-MNET
PROSOFT MVI94-GSC
PROSOFT MVI56-MCM
PROSOFT MVI94-MCM
PROSOFT MV156-PDPMV1
PROSOFT AN-X2-AB-DHRIO
PROSOFT PLX31-EIP-MBTCP
PROSOFT MVI56E-MCM
PROSOFT MVI69E-MBTCP
PROSOFT MVI46-PDPS
PROSOFT MV156E-MCMR
PROSOFT MVI46-ADMNET
PROSOFT MVI69E-MBS
PROSOFT MVI56E-MNET
PROSOFT MV169-MCM
PROSOFT MVI46-MCM
PROSOFT MVI56E-MNET
PROSOFT MVI56-EGD
PROSOFT MVI69-MCM
5204-MNET-PDPMV1
MVI46-DFNT

Additional information

Weight 0.1 kg
Dimensions 10 × 10 × 10 cm